English German

How can the energy meter be read?

  • It should be noted that the A2000 has a total of 8 internal energy meters that are always active. Depending on the energy mode set (see "Energy" configuration menu), the following distribution applies:

MODE: L123

  • Active energy meter for phases 1, 2, 3 and total
  • Reactive energy meter for phases 1, 2, 3 and total
  • (count upwards on supply and downwards on discharge)

MODE: LTHT

  • Active energy meter for LT supply, LT release, HT supply, HT release
  • Reactive energy meter for LT consumption, LT delivery, HT consumption, HT delivery

Attention: The meter readings are deleted when the energy mode is changed!